Sensorwell

2450A 02950007

2450A Series Heat Detection Thermostats
The 2450A Series are designed for use in both photoelectric and ionization type smoke detectors. The gold alloy contacts open or close on a temperature rise of 47 °C to 107 °C [117 °F to 225 °F]. They are epoxy sealed for long life and are available with or without heat collectors.

Request now

2450A 02950007

Produkt Merkmale

Kenndaten

  • Gold alloy contacts
  • Epoxy-sealed cap
  • Epoxy-sealed terminals

Anwendungsbereiche

  • Fire alarms
  • Smoke detectors
  • Security devices

Technische Daten

Functional Properties
Close on rise
Reset Type
Automatic
Operating Temperature
47 °C to 107 °C [117 °F to 225 °F]
Amperage
3.0 A
Voltage
120 Vac
Open Temperature
61.7 °C [143 °F] min.
Open Tolerance
N/A
Close Temperature
87.8 °C [190 °F]
Close Tolerance
3.9 °C [7 °F]
Environmental Exposure Range
0 °C to 150 °C [32 °F to 302 °F]
Dielectric Strength
MIL-STD-202, Method 301; 2000 Vac 60 Hz - Terminal to Case
Insulation Resistance
MIL-STD-202, Method 302; Cond. B - 500 MOhm - 500 Vdc applied
Contact Resistance
MIL-STD-202, Method 307; 0.050 Ohm
Housing Material
Phenolic, epoxy seal cap and terminals
Contact Material
WE -1 gold alloy cross point
Mounting
Stepped aluminum cap
Agency Approvals and Standards
UL
Comments
Heat detection
Series Name
2450A

We are happy to help you!

Inquire now

Our partners

Kalsdorfer Straße 26 a
8073 Feldkirchen bei Graz
Austria

Tel:    +43 316 40 33 01